Deaerator Heat Balance Calculator

Feedwater deaeration · steam/water heat balance

Open Calculator →

Compute the heating-steam demand of a feedwater deaerator from an energy and mass balance on IAPWS-IF97 enthalpies: m_feed·h_feed + m_steam·h_steam = (m_feed+m_steam)·h_out, with h_out the saturated-liquid enthalpy at the deaerator pressure. Covers atmospheric (~104C) and pressurized (130-160C) types.

Inputs

ParameterNotes
Feedwater flow (kg/h)Makeup + condensate
Feedwater temp (C)Subcooled inlet
Deaerator pressure (kPa abs)Sets outlet sat. T
Heating steam pressure/tempSaturated or superheated

Outputs

OutputBasis
Heating steam (kg/h)From the balance
Steam fraction of feed (%)Sizing check
Outlet water flow & enthalpyDeaerated water

Standards & Method

Steam/water energy and mass balance on IAPWS-IF97 enthalpies. Add ~0.1-0.5% vent steam and confirm O2 stripping performance for design.

Open the Deaerator Heat Balance Calculator →

Screening-level preliminary calculation. Verify against project standards and vendor data before engineering use.